FEATURES
? Operating voltages: 230VAC, 115VAC, 24VAC, 24VDC
? Both models listed for high temperature applications
? Interconnect up to 30 units for common functions
? UL, CUL, CSFM, and MEA Listed
? Compact Size
? Two sets of 10A form “C” alarm contacts
? One set of 10A form “C” trouble contacts
? Rugged steel back box with clear cover
? Compatible with the WP-1 weatherproof enclosure
? Easy retro-fit/upgrade of existing RW Series detectors
? Clear cover fitted with 4 captive screws
? Large terminal connection screws
? Interchangeable “Plug-In” photoelectric or
ionization heads
? Easy mounting without cover removal
? Advanced detector head design yields internal
dust filtering with no additional screens or filters to clean
? Over 15 remote accessories available
The SM-501 Series Duct Smoke Detector
PRODUCT SPECIFICATIONS
MODEL NUMBER:
|
SM-501-N
|
Ionization: 230VAC, 115VAC, 24VAC, 24VDC
|
|
SM-501-P
|
Photoelectric: 230VAC, 115VAC, 24VAC, 24VDC
|
DETECTOR HEAD MODEL NUMBER:
|
SM-501-N
|
55000-250APO or 55000-225APO
|
|
SM-501-P
|
55000-350APO or 55000-328APO
|
SAMPLING TUBES:
|
FAST Tube
|
Sectional sampling tube, kit fits up to 90” duct width
|
|
STS-1.0
|
Sampling tube for 12” or less duct width
|
|
STS-2.5
|
Sampling tube for 6” to 2.5’ duct width
|
|
STS-5.0
|
Sampling tube for 2.5’ to 5.0’ duct width
|
|
STS-10.0
|
Sampling tube for 5.0’ to 10.0’ duct width
|
เอกสารแนบ
|