Globe valve, 2-way, Flange, PN 25 • For closed (high temperature) hot water and steam systems in the non-critical range • For water-side modulating control of air-handling and heating systems
Type
|
DN
[ ]
|
kvs
[ m³/h]
|
Stroke
[ mm]
|
PN
[ ]
|
Sv min.
[ ]
|
H6015XP4-S2
|
15
|
0.4
|
15
|
25
|
50
|
H6015XP63-S2
|
15
|
0.63
|
15
|
25
|
50
|
H6015X1-S2
|
15
|
1
|
15
|
25
|
50
|
H6015X1P6-S2
|
15
|
1.6
|
15
|
25
|
50
|
H6015X2P5-S2
|
15
|
2.5
|
15
|
25
|
50
|
H6015X4-S2
|
15
|
4
|
15
|
25
|
50
|
H6020X4-S2
|
20
|
4
|
15
|
25
|
100
|
H6020X6P3-S2
|
20
|
6.3
|
15
|
25
|
100
|
H6025X6P3-S2
|
25
|
6.3
|
15
|
25
|
100
|
H6025X10-S2
|
25
|
10
|
15
|
25
|
100
|
H6032X10-S2
|
32
|
10
|
15
|
25
|
100
|
H6032X16-S2
|
32
|
16
|
15
|
25
|
100
|
H6040X16-S2
|
40
|
16
|
15
|
25
|
100
|
H6040X25-S2
|
40
|
25
|
15
|
25
|
100
|
H6050X25-S2
|
50
|
25
|
15
|
25
|
100
|
H6050X40-S2
|
50
|
40
|
15
|
25
|
100
|
H6065X58-SP2
|
65
|
58
|
18
|
25
|
100
|
H6080X90-SP2
|
80
|
90
|
18
|
25
|
100
|
H6100X125-SP2
|
100
|
125
|
18
|
25
|
100
|
Functional data
|
Media
|
Hot water and steam ( ?p/P1 <0.4), water with
max. 50% volume of glycol
|
|
Medium temperature
|
5...150°C
|
|
Medium temperature note
|
120°C up to 2500 kPa
150°C up to 2430 kPa
|
|
Permissible pressure ps
|
2500 kPa
|
|
Flow characteristic
|
equal percentage (VDI/VDE 2173) n(gl) = 3,
optimised in the opening range
|
|
Leakage rate
|
max. 0.05% of the kvs value
|
|
Pipe connectors
|
Flange according to ISO 7005-2 (PN 25)
|
|
Closing point
|
Bottom (?)
|
|
Installation position
|
Upright to horizontal (in relation to the stem)
|
|
Maintenance
|
Maintenance-free
|
Materials
|
Housing
|
GGG 40.3
|
|
Closing element
|
Stainless steel
|
|
Stem
|
Stainless steel
|
|
Stem seal
|
PFTE V-ring
|
|
Seat
|
Stainless steel
|
|